My October 2026 article on motor conductors, motor ratings and National Electrical Code letters covered basic, but essential concepts. This month’s article addresses code letter requirements, explains how to determine locked-rotor values and provides additional information on new motor designs in the 2026 NEC.
Existing NEC Table 430.251(A) lists locked-rotor currents for single-phase motors; Table 430.251(B) lists locked-rotor currents for three-phase Design B, C and D motors; and new Table 430.251(C) lists locked-rotor currents for three-phase design BE and CE motors. NEC 430.7(A)(9) requires motor nameplates to include the design letter for design A, B, BE, C, CE and D motors. NEC 430.7(A)(9), Informational Note No. 2 provides information on motor design letter definitions in ANSI/NEMA MG 1-2016, covering definitions of motors and generators, Part 1. We will address these new motors after first explaining motor locked-rotor calculations.
The requirement for locked-rotor current is located in NEC 430.7(A)(7), which states an AC motor rated at 0.5 horsepower or more must have a locked-rotor indicating code letter on the nameplate of the motor. NEC 430.7(B) and Table 430.7(B) provide the values for code letters A through V for the low and high kilovolt-amperes (kVA, or 1,000 VA) per horsepower (locked-rotor current values) of a motor. A motor with a code letter A has much less locked-rotor current (startup current) than a motor with the same horsepower and a code letter V. For example, a code letter G motor will have a low locked-rotor current of 5.6 kVA to a high of 6.29 kVA per horsepower.
Assuming a 10-horsepower motor with a code letter G, the lower and upper calculation would be 10 × 5.6 kVA = 56 kVA on the low side and 10 × 6.29 kVA= 62.9 kVA on the high side. If the motor is 480V three-phase, we first multiply 480V by the square root of three (1.732): 480V × 1.732 = 831.36V. Then we divide the high or low startup current by that value. So for the low startup current, 56 kVA ÷ 831.36V = 67.4A. For the high startup current, 62.9 kVA ÷ 831V = 75.7A. The normal running current (full-load current) for that motor, based on NEC Table 430.250, would be 14A.
As can be seen, the startup current is much greater than the running current. The purpose of the code letter for a motor is to address a number of different issues with a motor, such as helping to determine the type of overload protection for the motor and providing the values of motor contribution [see NEC 240.86(C)] in a short-circuit or ground-fault situation. In these situations, the motor will act as an additional source of fault current.
As previously mentioned, Article 430 in the 2026 NEC has incorporated new NEMA design BE and design CE motors. Design BE motors are advanced versions of traditional NEMA motors with a focus on improved energy efficiency and performance. These new motor designs are provided in the NEMA MG-1 standard (the motor and generator design manual). BE and CE motors are designed to meet stricter efficiency standards and reduce energy consumption compared to traditional designs (A, B, C and D) that help reduce operational costs and are suitable for various industrial applications where energy efficiency is critical.
Be careful, however, because the higher efficiency levels in BE and CE motors will have increased locked-rotor startup current values that will affect the type and size of circuit breakers and fuses as well as overload protection for these motors.
For example, NEC 430.32(A) allows overload protection for motors with a marked service factor of 1.15 or greater or motors with marked temperature rise of 40°C or less with an overload device rated at 125% of the motor nameplate. These new BE and CE motors may require using NEC 430.32(C). This section states that where the sensing element or setting or sizing of the overload device selected in accordance with 430.32(A)(1) and 430.32(B)(1) is not sufficient to start the motor or to carry the load, higher-size sensing elements or incremental settings or sizing are permitted to be used, provided the trip current of the overload device does not exceed 140% of the motor nameplate full-load current rating for motors with a marked service factor of 1.15 or a marked temperature rise of 40°C or less.
NEC 430.32(C), Informational Note allows Class 20 overload relay with a longer motor acceleration time than a Class 10 or Class 10A overload relay. A Class 30 overload relay will provide a longer motor acceleration time than a Class 20 overload relay. Use of a higher-class overload relay may preclude the need for selection of a higher trip current. Using a time-delay overload relay may be the answer for these new motors.