A Change in Editions: 2027 NFPA 70E update, part 4

By Jim Phillips | Nov 17, 2026
AdobeStock_2166327389
In Part Four of this series on major changes to the 2027 edition of NFPA 70E, we’re looking at Article 100, major revisions to Informative Annex K and new Informative Annex T.

Advertisement

Advertisement

Advertisement

Advertisement

Advertisement

In Part Four of this series on major changes to the 2027 edition of NFPA 70E, we’re looking at Article 100, major revisions to Informative Annex K and new Informative Annex T.


New definitions in Article 100

Definitions are important. A “lively” debate about the meaning of an NFPA 70E requirement can ultimately come down to the definition of a single word or phrase. 

Several definitions were added to Article 100, including:

  • Electric double layer capacitor (EDLC): A device with properties of capacitors and electrochemical cells that store energy in a non-Faradaic manner using an electrode-­electrolyte interface. This supports new Article 370, Safety-­Related Work Practices for Electrical Double Layer Capacitors. 
  • Contact thermal hazard: A source of possible injury or damage to health from contact with heat dissipated by a conductive object as it conducts current. 
  • Shorting stick: A device used to discharge a capacitor from terminal to terminal.

Deleted definitions

Several definitions were deleted because they are no longer used or are unnecessary in NFPA 70E. These include terms such as “competent person,” “electrical safety,” “pilot cell” and “safeguarding.”


Revised definitions

Other definitions were revised for clarity or to reflect changes elsewhere.

  • Electrically safe work condition: A new informational note references 110.2(C) and 120.2 through 120.6 for the requirements necessary to establish and verify an electrically safe work condition. 
  • Ground stick: The words “and to ground” were added. Previously, the definition said to apply the ground stick to capacitor terminals without mentioning ground. 
  • Arc blast hazard: The word “supersonic” was added: “acoustical supersonic shock wave and high-velocity shrapnel.” 
  • Electric shock hazard: The informational note was deleted because it was incomplete and did not address all types of electric shock hazards. 
  • Electrical hazard: A new Informational Note No. 1 references Informative Annex K for additional information on electrical hazards. 
  • Hard grounding: The text “capacitance by connecting to ground” was added to the definition. A new informational note provides guidance for ungrounded capacitors: “Capacitors that are ungrounded will not discharge unless the discharge resistor is connected between terminals.”
  • Soft grounding: The text was changed to “discharging capacitance by connecting to ground” through a power resistor to avoid hazards associated with “a low-­impedance short circuit.” The same new informational note in hard grounding’s definition was also added. 

Many terms in Article 100 of NFPA 70E also appear in NFPA 70, National Electrical Code. Some have had slightly different definitions. Where appropriate, definitions were revised to align with the 2026 NEC. Definitions extracted from the NEC are identified by a source reference following each one.


Major revision of Informative Annex K

Informative Annex K, General Categories of Electrical Hazards, received a substantial revision and expansion for the 2027 edition. 

The revised annex updates information on electrical injuries and hazards. It emphasizes that electrical incidents are not limited to electrical workers in traditional electrical occupations. The data highlights incidents involving nonelectrical workers and work on or near energized electrical equipment. It also emphasizes systems operating at 250V or less, reinforcing that serious hazards are not limited to higher-voltage installations. Annex K identifies electric shock and arc flash as the general categories of electrical hazards NFPA 70E addresses. It also recognizes contact thermal hazards from conductive objects heated by electric current. 

The expanded annex addresses electric shock effects, including thermal injury, nervous system effects and potential long-term consequences. Its arc flash discussion covers thermal, mechanical, acoustic and light energy. The release of mechanical energy, arc-resistant equipment, standing to the side and the use of remote racking are discussed. 


New Informative Annex T

The new Informative Annex T provides background on EDLC technology. EDLCs do not present the same arc-blast risk from an extremely rapid rise in fault current or the associated acoustic shockwave capable of causing lung damage as conventional capacitors. However, arrays of EDLCs can still expose workers to electric shock, thermal and arc-flash hazards.

Most individual EDLC cells operate below 3V DC, compared with conventional capacitor technologies operating well above 100V DC. Higher EDLC operating voltages are achieved by connecting multiple cells in series. This produces a significantly higher equivalent series impedance than conventional capacitors, helping limit the rate of fault current rise.


Definitions and annexes

Though less prominent than other articles, changes to Article 100 and informative annexes provide terminology and technical context for applying the 2027 NFPA 70E. These changes help connect terminology with practical hazard recognition and application of the work practices found throughout the standard.

This article is based on my views and does not represent an official position of the NFPA.