Recently, I received a phone call from an electrical contractor friend who was discussing with an electrical inspector the differences of branch circuits supplying swimming pool equipment versus swimming pool equipment feeder circuits at an existing home.
The swimming pool in question was built in 2011, so the existing feeder for most of the pool equipment was installed based on the 2011 National Electrical Code (NEC). The homeowner wanted to add branch circuits from a new 100-ampere (A) panelboard for an auxiliary building to also supply electric pool water heaters. The new 100A panelboard was supplied by a service entrance cable with two insulated ungrounded conductors, an insulated grounded conductor and an uninsulated equipment grounding conductor. Could my friend install the branch circuits to the new pool heaters from that panelboard?
The inspector said no, and my friend called me for a second opinion. Since the pool was installed in 2011, he felt he could install the branch circuits based on the 2011 NEC. I told him the answer was no and explained why.
Section 680.25(A) in the 2011 NEC stated feeders for swimming pool equipment must be installed in rigid metal conduit or intermediate metal conduit. If the wiring methods were not subject to physical damage, the following could be used for feeders to pool equipment: liquidtight flexible nonmetallic conduit, rigid polyvinyl chloride conduit, reinforced thermosetting resin conduit, electrical metallic tubing where installed on or within a building, electrical nonmetallic tubing where installed within a building, and Type MC cable where installed within a building and not subject to a corrosive environment.
However, due to the corrosive effects of swimming pool water chemicals, aluminum conduit could not be used for enclosing pool feeders. Section 680.25(B) in the 2011 NEC required pool feeder circuits enclosed in the wiring methods mentioned in 680.25(A) to have an equipment grounding conductor between the service equipment and the pool panelboard or between a separately derived system and a pool panelboard.
This equipment grounding conductor was required to be insulated. However, the 2011 NEC contained an exception to 680.25(A) that stated an existing feeder between an existing remote panelboard and service equipment shall be permitted to be installed in flexible metal conduit (flexible metal conduit will corrode) or an approved cable that includes an equipment grounding conductor within its outer sheath. Permitting a cable assembly with an uninsulated equipment grounding conductor within the cable covering would have permitted the existing panelboard to supply pool equipment.
Furthermore, text in 680.25(B) alluded to the exception in 680.25(A) as follows: For other than (1) existing feeders covered in 680.25(A), Exception, or (2) feeders to separate buildings that do not utilize an insulated equipment grounding conductor in accordance with 680.25(B)(2), the equipment grounding conductor must be insulated.
The installation my friend was involved with would have been acceptable in the 2011 NEC.
This exception in 680.25(A) and the accompanying text in 680.25(B) was deleted in the 2014 NEC to ensure insulated equipment grounding conductors are installed for all swimming pool circuits, whether the feeders or branch circuits are existing or not. The introductory text in 680.25 is the same for the 2014 and the 2017 NEC, and it states the provisions for feeders apply to any feeder on the supply side of panelboards that supply branch circuits for pool equipment covered in Part II of Article 680 on the load side of the electrical service or the source of a separately derived system.
There was some controversy during the 2014 NEC process involving the deletion of the exception in 680.25(A) and the corresponding text in 680.25(B). The issue involved the definition or use of the word “existing” in both the exception and the other associated text mentioned above. Some Code people said, as soon as a panelboard was installed, it was existing and, as such, the installing contractor would then use the exception and not install an insulated equipment grounding conductor. When the exception and the text was inserted into the NEC, the word “existing” was intended to apply to new pool installations for existing buildings after construction on the main buildings was finalized and after the building’s final inspection.
It is interesting to me that many existing pool installations were installed using the original text. These changes didn’t occur until the 2014 NEC where the word “existing” was being misapplied or misunderstood.
About The Author
ODE is a retired lead engineering instructor at Underwriters Laboratories and is owner of Southwest Electrical Training and Consulting. Contact him at 919.949.2576 and [email protected].