Arcing Short-Circuit Current: 2018 IEEE 1584, Part 2

By Jim Phillips | Mar 15, 2019
Arc Flash Safety 0319 Photo Credit: Shutterstock / ra2studio
After my January column, we continue to explore the many changes in the 2018 edition of IEEE 1584, Guide for Performing Arc-Flash Hazard Calculations.

Advertisement

Advertisement

Advertisement

Advertisement

Advertisement

After my January column, we continue to explore the many changes in the 2018 edition of IEEE 1584, Guide for Performing Arc-Flash Hazard Calculations. When calculating the incident energy and arc flash boundary as part of an arc flash study/risk assessment, one of the main variables is the arcing short-circuit current. This is not the same as the traditional “bolted” short-circuit current that is often used to evaluate the interrupting rating of protective devices. The “arcing” short-circuit current flows across an air gap during an arc flash and, because of the additional impedance from the arc, is always less than the bolted short-circuit current.

Why would less current be so important? It seems like more current would be worse. It is because another important variable is the duration of the arc flash, which is normally defined by how long it takes an upstream protective device to trip. The lower arcing current may cause a protective device to take longer to trip—resulting in a greater (and more dangerous) incident energy.

1980s—No arcing current

There has been quite an evolution in how the arcing short-circuit current is handled. Back in the 1980s—the early days of arc flash calculations—equations were quite primitive by today’s standards. In fact, the arcing current was not even considered; only the bolted short-circuit current was used. When determining how long a protective device may take to operate, using the bolted short circuit could indicate the protective device would trip instantaneously, resulting in a lower incident energy. However, the lower (and unknown) arcing current could actually result in the device taking longer to trip.

2000—Bolted current and 38%

NFPA 70E Annex D.3 lists equations from a technical paper published in 2000. These equations are based on actual arc flash testing—a significant improvement. However, there was still no equation for calculating the arcing current. Instead, this method contains a workaround for arcing current, which states: “For 480-volt systems, the industry accepted minimum level for a sustaining arcing fault is 38 percent, of the available bolted fault.” That was it. Just multiply the bolted fault current by 38 percent, and evaluate the lower current to see if it resulted in a longer device clearing time and a worst-case incident energy.

2002—Arcing current and 85%

When the first edition of IEEE 1584 was published in 2002, one of more significant improvements was the introduction of arcing short-circuit current equations. However, since there could be many unknown factors that influence the actual arcing current, it was commonly referred to as an “estimate.” What if the actual arcing current was lower? It could again possibly result in the protective device taking longer to operate and lead to a greater incident energy.

The solution? Add an additional step where the estimated arcing current would be multiplied by 85 percent and the protective device operating time would be re-evaluated with the slightly lower current. The 100 percent case and 85 percent case would be compared, and the worst case would be used for the study result. The 85 percent multiplier was used for all arcing current calculations for systems under 1,000 volts (V).

2018—Arcing current and VarCf

Based on almost 2,000 new arc flash tests, the 2018 edition of IEEE 1584 has made further improvements to the arcing current calculations for greater accuracy. However, the new equations are more complex and include different electrode configurations, 10 different coefficients as well as other variables. The process involves several calculation steps including determining the “Intermediate Average Arcing Current” with equations based on 600V, 2,700V and 14,300V. The second step is to use the intermediate current(s) and solve for the final arcing current at the specific system voltage.

Similar to the 2002 edition, a second arc duration is calculated using a reduced arcing current to determine if there is an effect on the protective device operating time. Unlike the fixed value of 85 percent used in the 2002 edition, the 2018 edition has introduced a new equation for an Arcing Current Variation Correction Factor VarCf which is used for all voltages from 208V to 15,000V. The VarCf is heavily voltage dependent and has the greatest impact at voltages between 208V to 600V.

The evolution continues

It has taken several decades, hundreds of people, tens of thousands of man-hours and millions of dollars in research to move our understanding of arc flash and related calculations to this level. Some say the cost and time is too much. Electrical workers who have survived an arc flash with minimal or no injuries because of this effort know it is well worth it.