Doing the Math: Calculating lighting factors, part 2

By Mark C. Ode | Nov 13, 2026
Doing the Math: Calculating lighting factors, part 2
I believe many electrical contractors and engineers will miss this change. 

Advertisement

Advertisement

Advertisement

Advertisement

Advertisement

As I wrote In my column last month, the difference in the 2023 and 2026 National Electrical Code editions is between 120.13 for the minimum unit load for dwelling unit branch circuits at 3 VA per square foot, which is unchanged, and NEC 120.41 for feeder and service minimum unit loads at a new value of 2 VA per square foot instead of 3 VA per square foot. This section applies to one-family, two-family and multifamily dwelling feeder and service loads, so this overall unit calculation change will affect new installations.

I believe many electrical contractors and engineers will miss this change. Some may not understand how to calculate the branch circuit versus the feeder and service loads for the 2026 NEC. October’s article explained why Panel 2 changed the feeder and service calculation at 2 VA per square foot versus the branch circuit calculation that stayed at 3 VA per square foot: basically, the change was due to the major use of LEDs and the reduction in feeder and service loads that occurred because we are no longer installing incandescent lighting.


Necessary calculations

This article will provide an example of the calculation in Annex D1(a) of the 2026 NEC. This example calculation is for a two-story single-family dwelling. The first floor measures 30 feet by 30 feet (or 900 square feet) and the second floor measures 30 feet by 20 feet (or 600 square feet), for a total of 1,500 square feet. This dwelling has an unfinished cellar and attic, both not adaptable for future use, and two open porches. The appliances are a 12-kilowatt (kW), 120/240V range and a 5.5-kW, 120/240V clothes dryer. 

The general lighting and general-use receptacle load is based on the outside dimensions of the building, apartment or other area involved in accordance with NEC 120.5(C). For a dwelling unit, the floor area does not include open porches, detached garages or, as stated in the opening paragraph of Example D1(a), “an unfinished cellar not adaptable for future use.” A point to consider regarding this statement is that many basements or cellars could be suitable for conversion to family rooms, bedrooms, home offices or other habitable areas. In such instances, the space may need to be included in the general lighting load calculation.

The general lighting load for the feeder or service is 1,500 ft2 at 2 VA/ft2 = 3,000 VA. For the minimum number of branch circuits required, see NEC 210.11(A). The general lighting load for branch circuits in the dwelling unit, based on NEC 120.13, is 1,500 ft2 at 3 VA/ft2: 1,500 ft2 × 3 = 4,500 VA. Then divide that 4,500 VA by 120V = 37.5A of total lighting on the branch circuits. This requires three 15A, 120V branch circuits or two 20A, 120V branch circuits. 

For the small-appliance load of two 2-wire, 20A circuits, see NEC 210.11(C)(1). The laundry load is one 2-wire, 20A circuit. See NEC 210.11(C)(2). The bathroom branch circuit is one 2-wire, 20A circuit—no additional load calculation is required for this circuit. See 210.11(C)(3). 


Calculating the feeder size

Based on the preceding calculations, the minimum size feeder required, according to NEC 120.40, is the following: the general lighting load is 3,000 VA, plus the small appliance load of 3,000 VA, plus the laundry load of 1,500 VA, which gives us a total load of 7,500 VA. 

Based on NEC Table 120.45, the following calculation is permitted: the first 3,000 VA must be taken at 100%; of the 7,500 VA total minus that 3,000 VA (derived from the 100%) = 4,500 VA at 35% = 1,575 VA, plus the 3,000 VA from the 100%, which gives us a net load of 4,575 VA. Add the range load (based on NEC Table 120.55) at 8,000 VA plus the dryer load (based on NEC Table 120.54) at 5,500 VA, which provides a net calculated load of 18,075 VA. The net total load of 18,075 divided by 240V = 75A. 

NEC 230.42(B) and 230.79(C) require service conductors and disconnecting means rated not less than 100A. Calculating the neutral load for the feeder or service, based on only the unbalanced loads, is as follows: the lighting and small appliance load of 4,575 VA plus the range load of 8,000 VA at 70% (a load of 5,600 VA) based on NEC 120.61 plus the clothes dryer of 5,000 VA at 70% (a load of 3,850 VA): (5,600 VA + 3,850 VA) ÷ 240 V = 14,025 VA ÷ 240 V = 58A for the neutral. 

Obviously, this is a basic calculation with more complex calculations required for larger homes. 

stock.adobe.com/mariano

About The Author

ODE is a retired lead engineering instructor at Underwriters Laboratories and is owner of Southwest Electrical Training and Consulting. Contact him at 919.949.2576 and [email protected]. 