Testing Fire Alarm Equipment
What is the best code-compliant way to test each of these items on a periodic test? Take this quiz to check your knowledge.
1. Manual pull stations
Correct Answer: Activate as it would be used in an emergency
2. Smoke detectors
Correct Answer: Use canned smoke
3. Restorable heat detectors
Correct Answer: Either A or C
4. Nonrestorable heat detectors
Correct Answer: No testing is required
5. Water flow devices
Correct Answer: Flow water through the inspector’s test valve
6. O, S and Y valves
Correct Answer: Either B or C
7. Duct detectors
Correct Answer: Introduce smoke or aerosol into the duct detector and verify the sampling tubes properly sample the airflow
8. Horns
Correct Answer: Verify the horn sounds
9. Strobes
Correct Answer: Verify the strobe flashes
10. Speakers
Correct Answer: Verify the speaker sounds