Conductors and Circuit Requirements

Conductors and Circuit Requirements

Test your knowledge on conductor and branch circuit requirements in the National Electrical Code.

1. What NEC table is used to size wire-type equipment grounding conductors?

Correct Answer: 250.122

2. Which of the following is not recognized as an equipment grounding conductor?

Correct Answer: Mineral insulated (stainless-steel type)

3. If branch circuit conductors are adjusted in size because of correction factors, an increase in size is required for the associated equipment grounding conductor.

Correct Answer: False

4. What is the minimum size copper wire-type equipment grounding conductor for a feeder protected by a 1,000A rated circuit breaker?

Correct Answer: 2/0 AWG

5. Where necessary to comply with 250.4(A)(5) or 250.4(B)(4), the minimum sizes for wire-type equipment grounding conductors in Table 250.122 shall be increased.

Correct Answer: True

6. For an 80A branch circuit, liquidtight flexible metal conduit shall be permitted as an equipment grounding conductor, if the length does not exceed 6 feet.

Correct Answer: False

7. In a patient care space, the branch circuit must be installed in a raceway or cable that qualifies as an equipment grounding conductor and a wire-type, insulated, copper equipment grounding conductor must be included in the branch circuit.

Correct Answer: True

8. The circular mil area of a 6 AWG copper conductor is _______.

Correct Answer: 26,240

9. If a PVC conduit contains the following feeder circuits (200, 400 and 600), what is the minimum size aluminum equipment grounding conductor (wire-type) required to be installed?

Correct Answer: 2/0 AWG

10. Equipment grounding conductors perform which of the following functions?